4 61180001L1-5BSection 61180001L1-5, Issue 2
1. Flush-mount: For flush-mount systems, the Total
Access 1500 shelf must be mounted from the rear
of the rack, with mounting bracket flanges facing
rearward.
2. Mid-mount: For mid-mount systems, the Total
Access 1500 shelf must be mounted from the
front of the rack, with the mounting bracket
flanges facing forward.
NOTE
Other orientations will require either mounting
from the front or rear, and depend on the rack
type installed in the CO and the standard operating
procedures established by your CO.
Once the orientation of the shelf has been determined,
use the four appropriate screws for your CO rack and
an appropriate screwdriver and secure the Total
Access 1500 shelves in place on the rack.
Power Connections
Interconnections between the common card modules
and channel units are accomplished through the
backplane PCB. All external connections to the Total
Access 1500 are through connectors and wire-wrap
headers located on the backplane.
NOTE
When connecting power and ground wiring, be
sure to follow all local, national, and company
codes.
All permanent connections to the Total Access 1500
are made on the backplane. Figure 2 shows the
location of the power and ground connections, and
Figure 3 shows the backplane and pin-outs.
Frame Ground Connection
The frame ground terminal, located on the upper right
corner of the backplane (see Figure 3), should be
connected using appropriately sized wire. Use a wire
gauge that is at least the same gauge as the power
wiring. To make the frame ground connection to the
Total Access 1500:
1. Using the crimping tool, connect an appropriate
lug to each end of the appropriately sized wire.
2. Connect the ground wire from Total Access 1500
Frame ground terminal to the Equipment Rack
grounding screw.
3. Tighten the ground connection securely with a
straight-slot screwdriver.
Test Frame Ground Connection
To ensure a good ground, use a multimeter to check
continuity between the frame grounding lug and the
rack grounding strap at the top of the rack. Using a
voltmeter set to its lowest resistance range, if
applicable, place one lead on the rack’s ground strap
and the other lead on the Total Access 1500 frame
ground terminal. The reading should be 1 or 2 ohms.
Greater readings should be investigated.
Power Connection
NOTE
Connect to a reliably grounded -48 Vdc source,
which is electrically isolated from the AC source.
NOTE
A readily accessible disconnect device, such as a
rack mount fuse and alarm panel that is suitably
approved and rated, should be incorporated in the
fixed wiring.
Power connections use a block, labeled TB1, located
on the upper right side of the backplane (see Figure 2).
The terminals are on .375 inch centers and allow for
wire gauges up to 12 AWG. There is a separate Frame
Ground/External Ring Generator terminal, labeled
TB2, located on the bottom right side of the backplane,
and can accommodate up to 14 AWG wire. The Frame
Ground terminal routes to mechanical contact points
and provides an electrical connection to the chassis
metalwork.
Figure 2. Power and Ground Connectors
TB1
Pin Number Description
1 -48V IN PRI
2 -48V RTN PRI
3 -48V IN SEC
4 -48V RTN SEC
5 Frame Ground
TB1
IN
RTN
IN
RTN
Frame
Ground
-48 PRI
-48 SEC
1
5