
7 61180001L1-5B Section 61180001L1-5 Issue 2
Up to 14 dual LIU systems or 28 single LIU systems
may be daisy chained to a single output from the
timing source, so only one wire run is required from
the timing source for an installation of up to 14 or 28
Total Access 1500 shelves. Use wire of the same type
as was used for the wire run from the CO clock source
to the Total Access 1500 shelf. The following steps
provide instructions for connecting up to 14 or 28
Total Access 1500 shelves to a single external timing
source.
1. Determine the length of wire required to run from
the first shelf, connector P14, to the second shelf,
connector P14, which is to be wired in the same
daisy chain. Leave approximately 1 to 1 1/2
inches for wire-wrapping.
2. Using wire strippers, strip approximately 1 to 1
1/2 inches from both ends of the wire run.
3. Using a wire-wrap tool, wire-wrap the “+”, “–“
and drain wires to the “+”, “–” and ground
terminal pins of connector P14, CLK-OUT, on
the top of the backplane.
4. Run the wire from P14 on the “source” shelf to
connector P14, CLK IN, on the receiving shelf
(See Figure 4).
5. Wire-wrap the “+”, “–“ of the wire run to the “+”,
“–“ terminals of P14 on the receiving shelf.
6. At SW1 of the receiving shelf, mounted to the left
of P14, move the switch right to the “OUT”
position.
7. Repeat steps 1-6 for each Total Access 1500 shelf
that is to be interconnected on the single CO
timing source.
NOTE
In any daisy chain of Total Access 1500 shelves
using a single timing source, only the first shelf
in the chain should have the SW1 switch set to “
IN.” All the remaining shelves in the chain
should have SW1 set to “OUT.”
Wiring Test Access
A four-lead (T, R, I, and drain) common test access
bus is provided for metallic test access to all customer
loops and is labeled P6 on the backplane. If the Total
Access 1500 being installed will use these testing
features, wiring will be required to gain access to the
test leads.
Connect MLT
Metallic Loop test access is gained by wiring into the
connector P6, on the right side of the backplane.
The following steps are instructions for wiring the
Total Access 1500 for Metallic Loop test access.
1. After you have located the test loops and run them
to the Total Access 1500 shelf, use wire strippers
to strip approximately 1 to 1 1/2 inches from the
test leads.
2. Using the wire-wrap tool, wire-wrap the central
office “T” and “R” leads to the Total Access 1500
“R” and “T” pins, respectively, on terminal P6.
3. Wire-wrap the inhibit wire of the cable to the top
pin labeled “I” on P6.
4. Wire-wrap the drain wire of the cable to the
bottom pin labeled ground on P6.
5. Neatly tie down the test cable pair.
Alarm Connections
Alarming is dependent on how the Total Access 1500
system is configured. When the Total Access 1500 is
configured as a channel bank using a single or dual T1
feed, the alarm outputs should be represented by
VMJ(Visual Major), VMN(Visual Minor),
AMJ(Audible Major), AMN(Audible Minor),
AUX(Auxiliary) and -48. However, if the Total
Access 1500 bank is configured as a DLC using quad
T1 feed, the alarm outputs should be represented by
T1A(A Digroup Major), T1B(B Digroup Major),
T1C(C Digroup Major), T1D(D Digroup Major),
BANK(Bank System Major), and -48. In the DLC
mode, the Total Access 1500 separately monitors the
performance of each digroup (A, B, C and D) and the
bank. The DLC mode assures that an alarm at the
digroup level provides appropriate central office and
remote information.
The Total Access 1500 provides standard bank alarm
outputs. Each of the alarms listed below consists of a
three-pin wire-wrap header that connects to the SCU
for alarm management. The SCU provides the
necessary electronic circuits for a NO/COM/NC
contact arrangement. The alarms are:
• Major-Visual Output
• Minor-Visual Output
• Major-Audible Output
• Minor-Audible Output
• AUX Output
• ACO Alarm Input
The alarming configuration is selected as an LIU
option through the VT100 craft interface.
Kommentare zu diesen Handbüchern