176 © 2002 ADTRAN, Inc. 61200600L1-1A
Section 5 DLP-014 Total Access 600R System Manual
7. Set the failsafe timer by selecting S
YSTEM UTILITY>TERMINAL MODE and typing fstimer start x, (where
x is in seconds) at the > prompt. Select a value for x which will allow enough time for the service
provider to reconfigure the network to match the unit's new configuration and which will allow an extra
3 to 5 minutes for the unit to sync up with the network.
8. Type Save at the > prompt. This applies all configuration changes and the current connection is lost.
9. At this point, the service provider reconfigures the network to match the unit's new configuration.
10. After the network configuration is complete, the service provider attempts to connect to the unit. If the
connection is successful, deactivate the failsafe timer by selecting S
YSTEM UTILITY>TERMINAL MODE
and typing fstimer stop at the > prompt.
11. If the connection is not successful, wait until the timer expires and the unit will factory default back to
the A
UTO-CONFIG mode. Repeat Steps 4-10 of this DLP.
Follow-up Procedures
Once this procedure is complete, return to the procedure which referred you to this DLP and continue with
the tasks indicated there.
Set the failsafe timer prior to doing the save. Typing save will apply the configuration
changes, and the unit will not be accessible until the network is reconfigured.