Chapter 9. Transaction Language 1 (TL1)
9-32 MX2810 M13 User Manual 61185001L1-1
The following data dictionary (Table 9-10) contains entries that are
used to edit or retrieve options for the equipment portion of the
MX2810. When performing TL1 edit commands from this table, the
value of rr should be "EQPT" and the <aid> value should be one of
the following:
400 - All EQPT identifiers
401 - Generic
402 - Control Card A
403 - Control Card B
404 - Power Supply A
405 - Power Supply B
Table 9-10. TL1 Editing Data Dictionary for EQPT
Keyword Type Domain Description
DIAGBERTCLEARCOUNT Y/N Y or [N] Clears BERT Count.
DIAGBERTCOUNT INT 0, 1, 2, ..., N Error Count.
DIAGBERTSYNC ENUM One of the following:
NOSYNC
SYNC
Identifies state of Pattern
Synchronization.
DIAGLPBKTIMEOUT ENUM One of the following:
DISABLE
•1-MIN
•5-MINL
10-MIN
15-MIN
30-MIN
45-MIN
•1-HR
Identifies the amount of time before a
Diagnostic Loopback will timeout.
DIAGRESET Y/N Y or [N] Resets Diagnostic Loopbacks.
PSBATTERYLOWRLY Y/N Y or [N] Identifies status of Power Supply
Battery Low alarm relay.
Yes (Y) - enables alarm
No (N) - disables alarm
PSCHARGERFAILRLY Y/N Y or [N] Identifies status of Power Supply
Charger Fail alarm relay.
Yes (Y) - enables alarm
No (N) - disables alarm
PSMALFNCRLY Y/N Y or [N] Identifies status of Power Supply
Malfunction alarm relay.
Yes (Y) - enables alarm
No (N) - disables alarm