Appendix A. Acceptance Test Procedure
A-16 MX2810 M13 User Manual 61185001L1-1
• Disabled – No signal continuity exists through the MX2810 and no
alarms are detected or transmitted.
• Enabled – Signal continuity and alarming are always enabled.
• Auto Enable (default) – Signal continuity and alarming exist only
after a DS1 signal is detected at the DS1 input to the MX2810.
Once a signal is detected, the only
way to disable alarming is to
momentarily toggle the DS1 channel to the Disable state as
follows:
From the Main Menu, select Configuration (3), T1/E1 Interface (2) and
T1 State (1). From the T1/E1 State screen, enter the DS1# in question,
and then select Disabled (1) to disable signal continuity and alarm
transmission. Repeat the process of selecting the DS1 from the T1/E1
State screen, but this time select Auto Enable (3) to once again provision
the slot/channel for service. No alarms will be transmitted until a DS1
signal has been detected and removed or an unframed signal is detected.
FINAL SYSTEM CONFIGURATION
(TRAFFIC READINESS)
After the previous tests are successfully completed and the default settings
are restored, the MX2810 can be considered ready for customer traffic.
Specific provisioning of the DS3, DS1 and other options is determined by
circuit orders and local practices.